TYPE: CANOPY SILENT
PHASES: THREE PHASES
KVA: 100 KVA
The applicable voltage range is 380V to 415V for 50Hz applications. For other voltages, please consult factory.
This generating set is of fixed speed of 1500 rpm.
DT100 is the prime power rating of the generating set is where a variable load and unlimited hour usage are applied with an average load factor of 80% of the prime rating over each 24-hour period. Noting that a 10% overload is permitted for 1 hour in every 12-hour operation.
DT110S is the standby power rating of the generating set is where a variable load limited to an annual usage up to 500 hours is applied, with 300 hours of which may be continuous running. Noting that no overload is permitted.
Engine Technical Data
Make & Model / GSPU JOHN DEERE 4045HF120 / 4045HF158R
Cylinders & Arrangement 4; vertical in-line
Bore & Stroke (mm) 106 x 127 mm
Induction system Turbo Charged
Combustion Direct injection
Cycle4 stroke
Compression ratio 17.0:1
Cooling System Water cooled
Displacement 4.5 liters
Lube oil capacity 12 liters Max
Coolant capacity 25 liters
Standard governor (Optional) Mechanical (Electronic)
Engine Speed 1500 rpm
Fuel & Oil Consumption Fuel Cons. Oil Cons.
Consumption @ 100% Load (L/H) 21.3 0.060
Consumption @ 75% Load (L/H) 16.4 0.043
Consumption @ 50% Load (L/H) 10.9 0.029
Consumption @ 25% Load (L/H) 5.0 0.014
Radiator Cooling Air Flow (m3/s) 2.5
Emissions regulations For non-regulated territories
Exhaust temperature ᵒC (max) 565
Max exhaust gas flow (m3/min) 18.7
Max. allowed back pressure (kPa) 7.5
The above performance data are valid as per the following specs
* Diesel Fuel is according to BS2869 Class A2 or equivalent.
* Lubricating oil is according to Grade SAE 15W-40 API CI4.
* The coolant should be 50% antifreeze and 50% fresh water.
Alternator Technical Data
Make & Model Leroy Somer TAL044D
Frequency / No. of poles 50 Hz / 4P
Ingress protection IP23
Insulation class H
Terminals (Optional) 6 (12)
Excitation system SHUNT
Winding pitch 2/3
AVR model R120
Overspeed 2250 R.P.M.
Voltage regulation ± 1 %
Coolant air flow 0.25 m3/s
SIZE | CHEST(in.) | WAIST(in.) | HIPS(in.) |
---|---|---|---|
XS | 34-36 | 27-29 | 34.5-36.5 |
S | 36-38 | 29-31 | 36.5-38.5 |
M | 38-40 | 31-33 | 38.5-40.5 |
L | 40-42 | 33-36 | 40.5-43.5 |
XL | 42-45 | 36-40 | 43.5-47.5 |
XXL | 45-48 | 40-44 | 47.5-51.5 |
Weight | 23 kg |
---|---|
Dimensions | 12 × 24 × 35 cm |
Color | Black, Green, Indigo |
Size | Large, Medium, Small |
Excellent.